Intelligent Dry-Type Transformer Monitor is designed for the safe operation of dry-type transformer. It can automatically operates the fan's relay according to the temperature. By comparing the current temperature to a pre-selected temperature, the monitor operates an alarm and the relay trips to keep the transformer running safely.
Technical index:
Rail transit fiber optic temperature controller |
|
Fluorescent fiber optic sensing probe |
Ambient temperature: |
-20ºC~+55ºC |
|
Material: |
No metal material, quartz fiber |
Ambient humidity: |
< 95% (25ºC) |
Probe size: |
3mm in diameter;
Standard equipped with 3M(Customizable length) |
Working voltage: |
AC 220V (+10%,-15%) |
Immune electromagnetic interference
Withstand power frequency voltage 100KV |
Working frequency rate: |
50Hz OR 60Hz(±2Hz) |
Range of measurements: |
-40.0ºC~200.0ºC |
Measurement accuracy: |
±1%FS |
|
|
Resolution ratio: |
0.1ºC |
|
|
Fan output total capacity: |
9A/250VAC |
|
|
Control output capacity: |
5A/250VAC;5A/30VDC(resistivity) |
|
|
Standard of Execution:
Production standards |
JB/T7631-2005"Electronic temperature controller for Transformers"Industry standards |
Adoption of accreditation standards: |
ISO9001:2008International Quality Management System Certification |
Pass the test standard: |
IEC61000-4:1995 International standard |
GB/T17626-2008"Electromagnetic compatibility test and measurement techniques"standard |
Special temperature controller for rail transit |
1.Monitor up to three dry-type transformer windings; |
2.Built-in fan control, fan exerciser; |
3.Each temperature sensor has temperature compensation function |
4.When the monitor is turned off, the temperature value can be saved. |
5.LCD liquid crystal display, LED display lamp, operation button; |
6.Clock function; |
7.Alarm function for transformer door cabinet opening; |
8.1 pairs of over temperature alarm terminals (1 normally open, 1 normally closed); |
9.3 set of over temperature trip terminals (3 normally open and 3 normally closed) are provided; |
10.1 sets of fan remote transmission nodes (1 normally open, 1 normally closed); |
11.1 set of temperature controller power off alarm contacts (1 normally open, 1 normally closed); |
12.1 set of temperature controller fault alarm contacts (1 normally open, 1 normally closed); |
13. RS485 communication function, MODBUS-RTU protocol; |
Custom function |
1.According to customer demand, provide 4 channel 4~20mA analog current output function; |
2.According to customer requirements, provide fan fault judgment function, provide two fan fault alarm contacts ; |
3.1-8 channel optical fiber temperature measurement |
4.Many kinds of communication: industrial networking module, Ethernet communication, Profibus communication module and so on. |
5.According to customer needs, provides alarm function for winding and iron core temperature rise rate. |
Product Features:
Optical Fiber Temperature Controller for Rail Transit
Embedded installation
Model Number:SR-TL series
Dimension:442×558×140(mm)
Front view lateral view